R-Guard Installation Detail
Flashing Transition - Shelf Angle with Termination Bar
SS ThruWall Flashing
1.
Use FastFlash or Joint & Seam Filler to spot and cover the anchor bolts that attach the shelf angle to the structure. Allow product to skin over.
2.
Place drip edge metal on the horizontal lentil/shelf angle. Secure the drip edge to the lentil/shelf angle by wet-setting the edge metal into wet FastFlash placed on the horizontal ledge of lentil/shelf angle.
Install SS ThruWall flashing.
3.
Apply a bead of FastFlash or Joint & Seam Filler along the top of the up leg of the SS ThruWall flashing. Wet-set the termination bar.
4.
Mechanically fasten the termination bar.
5.
Trade sequencing may make wet-setting impractical, and it is not required.